Skip to content

Commit

Permalink
Add more documentation for input data for 3-phase proof-of-concept el…
Browse files Browse the repository at this point in the history
…ements.
  • Loading branch information
rdzman committed Apr 11, 2024
1 parent 19519f0 commit 0913006
Show file tree
Hide file tree
Showing 2 changed files with 140 additions and 8 deletions.
140 changes: 136 additions & 4 deletions docs/sphinx/source/howto/three-phase.rst
Original file line number Diff line number Diff line change
Expand Up @@ -143,10 +143,6 @@ Data Format

The prototype examples included in |MATPOWER| 8 simply define a few extra fields in the standard |MATPOWER| case struct for the three-phase elements. The example above uses |t_case3p_a|_. This is a case with 4 three-phase buses, connected via 2 lines and 1 transformer, with a three-phase generator representing the substation at bus 1 and a three-phase load at bus 4.

The data for the individual elements are found in the fields ``bus3p``, ``line3p``, ``xfrm3p``, ``load3p``, and ``gen3p`` fields of ``mpc``. The ``lc`` field contains the per-mile impedance parameters for different line construction configurations referenced by the individual lines.

Besides the fields for the individual elements, cases with three-phase elements are also expected to include ``freq``, the system frequency in Hertz, and ``base_kVA``, the system per-unit kVA base for three-phase portions of the network.

::

function mpc = t_case3p_a
Expand Down Expand Up @@ -216,6 +212,142 @@ Besides the fields for the individual elements, cases with three-phase elements
1 0.457541 0.15594 0.153474 0.466617 0.157996 0.461462 1.078 0.501648 0.384909 1.04813 0.423624 1.06502 15.0671 -4.86241 -1.85323 15.875 -3.09098 14.3254
];

The data for the individual elements are found in the fields ``bus3p``, ``line3p``, ``xfrm3p``, ``load3p``, and ``gen3p`` fields of ``mpc``. The ``lc`` field contains the per-mile impedance parameters for different line construction configurations referenced by the individual lines.

Besides the fields for the individual elements, cases with three-phase elements are also expected to include ``freq``, the system frequency in Hertz, and ``base_kVA``, the system per-unit kVA base for three-phase portions of the network.

Details of the data for the individual three-phase elements are summarized in the tables below.


``bus3p``
^^^^^^^^^

=== ========= =====================
Col Name Description — *see also* :class:`mp.dme_bus3p`
=== ========= =====================
1 busid unique 3-phase bus ID (positive integer)
2 type bus type: 1 = PQ, 2 = PV, 3 = reference (voltage ref + slack)
3 basekV nominal voltage in kV
4 Vm1 phase A voltage magnitude in p.u.
5 Vm2 phase B voltage magnitude in p.u.
6 Vm3 phase C voltage magnitude in p.u.
7 Va1 phase A voltage angle in degrees (nominal 0)
8 Va2 phase B voltage angle in degrees (nominal -120)
9 Va3 phase C voltage angle in degrees (nominal 120)
=== ========= =====================


``line3p``
^^^^^^^^^^

=== ========= =====================
Col Name Description — *see also* :class:`mp.dme_line3p`
=== ========= =====================
1 brid unique 3-phase line ID (positive integer)
2 fbus "from" bus ID
3 tbus "to" bus ID
4 status 1 = in-service, 0 = out-of-service
5 lcid line construction ID (to look up in ``lc`` table)
6 len line length in miles
=== ========= =====================


``xfmr3p``
^^^^^^^^^^

=== ========= =====================
Col Name Description — *see also* :class:`mp.dme_xfmr3p`
=== ========= =====================
1 xfid unique 3-phase transformer ID (positive integer)
2 fbus "from" bus ID
3 tbus "to" bus ID
4 status 1 = in-service, 0 = out-of-service
5 R resistance (p.u. on transformer base)
6 X reactance (p.u. on transformer base)
7 basekVA transformer per-unit power base in kVA
8 basekV transformer per-unit voltage base in kV
=== ========= =====================


``load3p``
^^^^^^^^^^

=== ========= =====================
Col Name Description — *see also* :class:`mp.dme_load3p`
=== ========= =====================
1 ldid unique 3-phase load ID (positive integer)
2 ldbus bus ID
3 status 1 = in-service, 0 = out-of-service
4 Pd1 phase A active power demand in kW
5 Pd2 phase B active power demand in kW
6 Pd3 phase C active power demand in kW
7 lpf1 phase A load power factor
8 lpf2 phase B load power factor
9 lpf3 phase C load power factor
=== ========= =====================


``gen3p``
^^^^^^^^^

=== ========= =====================
Col Name Description — *see also* :class:`mp.dme_gen3p`
=== ========= =====================
1 genid unique 3-phase generator ID (positive integer)
2 gbus bus ID
3 status 1 = in-service, 0 = out-of-service
4 Vg1 phase A voltage setpoint in p.u.
5 Vg2 phase B voltage setpoint in p.u.
6 Vg3 phase C voltage setpoint in p.u.
7 Pg1 phase A active power injection in kW
8 Pg2 phase B active power injection in kW
9 Pg3 phase C active power injection in kW
10 Qg1 phase A reactive power injection in kVAr
11 Qg2 phase B reactive power injection in kVAr
12 Qg3 phase C reactive power injection in kVAr
=== ========= =====================


``lc``
^^^^^^

=== ========= =====================
Col Name Description — *see also* :class:`mp.dme_line3p`
=== ========= =====================
1 lcid unique 3-phase line construction record ID (positive integer)
2 R11 resistance (p.u. per mile), element (1,1) of 3x3 matrix
3 R21 resistance (p.u. per mile), elements (2,1) & (1,2) of 3x3 matrix
4 R31 resistance (p.u. per mile), elements (3,1) & (1,3) of 3x3 matrix
5 R22 resistance (p.u. per mile), element (2,2) of 3x3 matrix
6 R32 resistance (p.u. per mile), elements (3,2) & (2,3) of 3x3 matrix
7 R33 resistance (p.u. per mile), element (3,3) of 3x3 matrix
8 X11 reactance (p.u. per mile), element (1,1) of 3x3 matrix)
9 X21 reactance (p.u. per mile), elements (2,1) & (1,2) of 3x3 matrix
10 X31 reactance (p.u. per mile), elements (3,1) & (1,3) of 3x3 matrix
11 X22 reactance (p.u. per mile), element (2,2) of 3x3 matrix
12 X32 reactance (p.u. per mile), elements (3,2) & (2,3) of 3x3 matrix
13 X33 reactance (p.u. per mile), element (3,3) of 3x3 matrix
14 C11 capacitance (nF per mile), element (1,1) of 3x3 matrix
15 C21 capacitance (nF per mile), elements (2,1) & (1,2) of 3x3 matrix
16 C31 capacitance (nF per mile), elements (3,1) & (1,3) of 3x3 matrix
17 C22 capacitance (nF per mile), element (2,2) of 3x3 matrix
18 C32 capacitance (nF per mile), elements (3,2) & (2,3) of 3x3 matrix
19 C33 capacitance (nF per mile), element (3,3) of 3x3 matrix
=== ========= =====================


``buslink``
^^^^^^^^^^^

=== ========= =====================
Col Name Description — *see also* :class:`mp.dme_buslink`
=== ========= =====================
1 linid unique 3-phase buslink ID (positive integer)
2 busid bus ID of single-phase bus
3 bus3pid bus ID of three-phase bus
4 status 1 = in-service, 0 = out-of-service
=== ========= =====================


Example Cases
-------------
Expand Down
8 changes: 4 additions & 4 deletions lib/+mp/dme_line3p.m
Original file line number Diff line number Diff line change
Expand Up @@ -12,7 +12,7 @@
% ``bus_fr`` *integer* bus ID (``uid``) of "from" 3-phase bus
% ``bus_to`` *integer* bus ID (``uid``) of "to" 3-phase bus
% ``lc`` *double* index into line construction table
% ``len`` *double* line length *(?)*
% ``len`` *double* line length *(miles)*
% ``pl1_fr`` *double* phase 1 active power injection at "from" end *(kW)*
% ``ql1_fr`` *double* phase 1 reactive power injection at "from" end *(kVAr)*
% ``pl2_fr`` *double* phase 2 active power injection at "from" end *(kW)*
Expand All @@ -36,11 +36,11 @@
% ``id`` *integer* unique line construction ID, referenced from
% ``lc`` column of main data table
% ``r`` *double* 6 resistence parameters for forming symmetric 3x3
% series impedance matrix
% series impedance matrix *(p.u. per mile)*
% ``x`` *double* 6 reactance parameters for forming symmetric 3x3
% series impedance matrix
% series impedance matrix *(p.u. per mile)*
% ``c`` *double* 6 susceptance parameters for forming symmetric 3x3
% shunt susceptance matrix
% shunt susceptance matrix *(nF per mile)*
% ====== ========= ==================================================