Notifications
You must be signed in to change notification settings - Fork 22
/
Copy pathcomap.py
145 lines (125 loc) · 5.4 KB
/
comap.py
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
import struct
import device
import probe
from register import Reg, Reg_s16, Reg_u16, Reg_u32b, Reg_text, Reg_mapu16
class Reg_Comap_ident(Reg, str):
""" The Comap controller returns an error if you don't read the entire 16
registers of the identification. But we don't want to use the entire 16
registers, we only care about the first 12 characters. This special
register allows us to read 16 registers, but only decode the 12
characters we care about. """
def __init__(self):
super().__init__(1307, 16)
def decode(self, values):
v = struct.pack('>16H', *values).rstrip(b'\0')
return self.update(v[:12].decode('ascii'))
class ComAp_Tank(device.CustomName, device.Tank, device.SubDevice):
raw_value_min = 0
raw_value_max = 100
raw_unit = '%'
def device_init(self):
self.data_regs = [
Reg_u16(1055, '/RawValue', 1, '%.0f %%', invalid=0x8000),
]
class ComAp_Generator(device.Genset):
vendor_id = 'comap'
vendor_name = 'ComAp'
productid = 0xB044
productname = 'Comap genset controller'
min_timeout = 0.5
reg_hole_max = 0
def device_init(self):
self.info_regs = [
Reg_text(1323, 8, '/FirmwareVersion'),
Reg_text(3000, 8, '/CustomName'),
Reg_mapu16(1301, '/NrOfPhases', {
0: 1, # single phase
1: 2, 2: 2, # Split phase
3: 3, 4: 3, 5: 3, 6: 3, 7: 3, # 3 phase
})
]
self.data_regs = [
Reg_s16(1020, '/Ac/Power', 0.001, '%.0f W'),
Reg_s16(1021, '/Ac/L1/Power', 0.001, '%.0f W'),
Reg_s16(1022, '/Ac/L2/Power', 0.001, '%.0f W'),
Reg_s16(1023, '/Ac/L3/Power', 0.001, '%.0f W'),
Reg_u16(1036, '/Ac/Frequency', 10, '%.1f Hz'),
Reg_u16(1037, '/Ac/L1/Voltage', 1, '%.0f V'),
Reg_u16(1038, '/Ac/L2/Voltage', 1, '%.0f V'),
Reg_u16(1039, '/Ac/L3/Voltage', 1, '%.0f V'),
Reg_u16(1043, '/Ac/L1/Current', 1, '%.0f A'),
Reg_u16(1044, '/Ac/L2/Current', 1, '%.0f A'),
Reg_u16(1045, '/Ac/L3/Current', 1, '%.0f A'),
Reg_u32b(1263, '/Ac/Energy/Forward', 1, '%.0f kWh'),
Reg_u16(1004, '/Engine/Speed', 1, '%.0f RPM', invalid=0x8000),
Reg_s16(1006, '/Engine/CoolantTemperature', 1, '%.1f C', invalid=-0x8000),
Reg_s16(1008, '/Engine/OilPressure', 10, '%.0f kPa', invalid=-0x8000),
Reg_u32b(1013, '/Engine/OperatingHours', 1/360, '%.1f s', invalid=0x80000000),
Reg_u16(1053, '/StarterVoltage', 10, '%.1f V'),
Reg_mapu16(1298, '/StatusCode', {
0: 1, # Init = Self-test
1: 0, # Ready = Stopped
2: 10, # Not ready = Error
3: 2, # Prestart = Preheat
4: 3, # Cranking = Starting
5: 3, # Pause = Starting
6: 3, # Starting
7: 8, # Running
8: 8, # Loaded (GCB is closed)
9: 9, # Unloading, GCB is open
10: 9, # Cooling
11: 9, # Stop
12: 9, # Shutdown
13: 9, # Ventilate (for petrol engines)
14: 10, # Emergency manual (controller does nothing)
15: 3, # Soft loading
16: 9, # WaitStop
17: 9 # Another kind of venting
}),
Reg_mapu16(1382, '/RemoteStartModeEnabled', {
0: 0, # OFF
1: 0, # MANUAL
2: 1, # AUTO
3: 0 # TEST
})
]
name = self.read_register(self.info_regs[1])
self.name = ''.join(filter(str.isalnum, name)).lower()
if self.read_register(Reg_u16(1055, invalid=0x8000)) is not None:
self.subdevices = [
ComAp_Tank(self, 0),
]
def get_unique(self):
# Use the custom name as identifier. Reasoning:
# 1. Cannot get the serial number from modbus
# 2. MAC address? It might be on a different subnet.
# 3. controller's default name is "InteliLite4", which is sane enough.
# 4. In the ComAp universe, this is already used to identify units on
# mobile connections, according to the manual. Page 222 of global
# manual.
return self.name
def device_init_late(self):
super().device_init_late()
# Fetch the current state of the coil and populate it
state = None
coils = self.modbus.read_coils(4700, unit=self.unit)
if not coils.isError():
state = int(any(coils.bits))
self.dbus.add_path('/Start', state, writeable=True,
onchangecallback=self._start_genset)
def _start_genset(self, path, value):
# This is documented in the Comap global manual, page 204.
# You need to write the relevant coil to stop/start the genset.
if value:
self.modbus.write_coil(4700, True, unit=self.unit)
else:
self.modbus.write_coil(4700, False, unit=self.unit)
return True
models = {
'InteliLite4-': { # InteliLite4-
'model': 'InteliLite 4',
'handler': ComAp_Generator,
}
}
probe.add_handler(probe.ModelRegister(Reg_Comap_ident(), models,
methods=['tcp'], units=[1]))